4 F.O 9/125 OS1/OS2 (FRNC/LSNH) IEC 60331-25/PH120
Armada acero corrugado (Full Rodent Protection)
Black UV resistant FRNC/LSNH outer jacket
Euroclase CPR: Cca-s1,d1,a1
A/I-DQ(ZN)(SR)H
Full Rodent Protection
Predicted lifetime > 30 years.
Safety
Testing standard | Description / Value | |
Reaction to fire |
IEC 60332-1 IEC 60332-3-22 EN 50575 |
Cca-s1,d1,a1 |
Circuit Integrity |
IEC 60331-25 EN 50200 |
E120: duration of test 120 minutes PH120: duration of test 120 minutes including shocks |
Toxicity | NF X 70-100-2 | |
Smoke density | IEC 61034-2 | |
Halogen acid gas content | IEC 60754-1 | Zero |
Degree of acidity of gases |
IEC 60754-1 IEC 60754-2 |
Min. 4.3 pH Max. 10 nS/mm |
Los precios no incluyen impuestos a no ser que se indique lo contrario.